Print Back

The FlowStat Paddle Wheel Flow Meter with integral sensor provides for very simple installation and operation. The sturdy Stainless Steel body provides durability and a long service life. FlowStat is offered with multiple outputs to choose from in addition to visual indication of flow through its optional clear cover where you can see the Rotor Flow. The straight fluid path and large spinning rotor means there is minimal pressure drop.

Applications include:

  • Chillers & Cooling Systems
  • Solar
more
Unit of Measure

Technical Specs

Manufacturer Name

AW-Lake Company

Type

Flowstat 30GPM Meter

Port Size Range

3/4" NPT

Medium

Fluid

Measuring Accuracy

±2% of full scale

Repeatability

±0.5% of full-scale

Flow Rate

30 gpm

Turn Down Ratio

10:1

Fluid Temperature Range

20-225°F (-7° to 107°)

Maximum Operating Pressure

14 bar200 psi

Filtration Requirements

150 Micron Filter recommended

Standard Calibration Fluid

Water at 70°F Temperature (21°C), 1.0 sg

Options

None

Process Port Type

3/4" NPT

Wetted Components Materials

Output

Voltage

Casing Material

Stainless Steel 316

Cover Material

Clear polycarbonate

Seal Material

Buna-N®

Impeller Material

Acetal Copolymer

Bearing Material

PEEK (Polyetheretherketone)

Shaft Material

316 Stainless Steel

Non-wetted Components Materials

Encapsulant Material

Epoxy

Strain Relief Material

Nylon

Lock Ring Material

Stainless Steel

Wire Insulation Material

High-Temperature PVC

Electronic Specifications

Power Requirements

12-24 VDC, Regulated

Maximum Current

25 mA DC, Regulated

Minimum Load resistance

1000 Ω

Maximum Transmission Distance

200 feet recommended

Resolution

Infinite

Response Time

< 5 seconds to 90% (step change)

Dimensions

A

3.06 in78 mm

B

1.33 in34 mm

C

2.46 in62 mm

D

2.88 in73 mm

E

5.25 in133 mm

F

3.80 in97 mm

Benefits

N/A

    Choice of Three Port Sizes
    Select from 1/2" , 3/4" or 1" NPT porting to meet system requirements.
    NOTE: Using reduced ID fittings will affect calibrated range.

    Encapsulated Circuitry
    Withstands the harshest environments.

    Several Outputs Available
    The standard interface is a 2-wire, 4-20mA current loop. Sensor signal may be transmitted on a low cost wire without degradation. Pulse, relay and 0-5 VDC (regulated) are also available.

    Connects Directly to your Flow Monitoring Instruments
    Can be connected directly to analog acquisition cards, chart recorders or other monitoring instruments, without external signal conditioning.

    Simply Plumb and Apply Power
    Comes factory calibrated to your flow range specifications.

Quick Ship

Quantity Available

Unknown

*1-5 Pieces

Unknown

*6-10 Pieces

Unknown

Std Lead Time

Unknown