Using the Transit Time measurement principle, the CUTT Clamp-On Ultrasonic Flow Meter fastens on the outside of vertical or horizontal pipes ranging in size from ½” through 48”.  Housed in a water- and dust-tight NEMA4X polycarbonate enclosure, the Clamp-On Ultrasonic Flow Meters offer Isolated 4-20 mA and 0-5 V analog output. The non-intrusive flow measurement allows measurement of the most “corrosive liquids” that would damage standard flow meters. Clamp-on transducers can accommodate all common pipe materials at diameters from 0.5” to 48” and withstand temperatures from -40°F to 300°F. The meter comes with free datalogging software for data display, manipulation, analysis, and exporting.  

Applications include:

  • Food processing
  • Chemical processing plants
  • Oil refineries
Unit of Measure
Items
Clamp-Ultrasonic-Flow-Meter

Clamp-on Ultrasonic Flow Meter
List Price $4,191.00

Clamp-Ultrasonic-Flow-Meter

Clamp-on Ultrasonic Flow Meter
List Price $4,553.00

Clamp-Ultrasonic-Flow-Meter

Clamp-on Ultrasonic Flow Meter
List Price $4,191.00

Clamp-Ultrasonic-Flow-Meter

Clamp-on Ultrasonic Flow Meter
List Price $5,007.00

Clamp-Ultrasonic-Flow-Meter

Clamp-on Ultrasonic Flow Meter
List Price $4,990.00
Manufacturer Name N/A AW-Lake Company
Type N/A Ultrasonic Flow Meter
Style N/A Clamp-on
Power Input N/A 100-240VAC, 50/60Hz, 10VA Max.
Enclosure & Electronics Protection N/A NEMA4X (IP66) polycarbonate enclosure
Enclosure Temperature Rating N/A -5 to 140 ºF-20 to 60 ºC
Intrinsic Safety Rating N/A No certification
Transducers N/A SE16A pair, clamp-on for 0.5" to 4" (15 mm to 100 mm) pipes, BNC connectors and IP65 rating N/A SE16A pair, clamp-on for 0.5" to 4" (15 mm to 100 mm) pipes, BNC connectors and IP65 rating N/A E16B pair, clamp-on for 2" to 48" (50 mm to 1200 mm) pipes N/A E16B pair, clamp-on for 2" to 48" (50 mm to 1200 mm) pipes N/A SE16C pair, recommended for 12" to 48" (300 mm to 1200 mm) pipes, suitable for 4" to 48" (100 mm to 1200 mm) pipes, BNC connectors and cable strain-relief fittings for IP67 rating
Transducer Mounting Hardware N/A TMK-A1 – Includes stainless track mount with built-in ruler, mounting clamps, and silicone coupling compound. Standard option for SE16A transducer pair. N/A TMK-A1 – Includes stainless track mount with built-in ruler, mounting clamps, and silicone coupling compound. Standard option for SE16A transducer pair. N/A TMK-B1; Includes stainless brackets, mounting clamps, alignment bar, and silicone coupling compound. N/A TMK-B1; Includes stainless brackets, mounting clamps, alignment bar, and silicone coupling compound. N/A TMK-C1 – Includes stainless brackets, mounting clamps, alignment bar with built-in ruler, and coupling tape for permanent installations. For 12" to 18" (300 mm to 450 mm) pipes.
Cables & Connections N/A 25 ft/7.6 m pair triaxial with BNC connectors and seal jackets N/A 25 ft/7.6 m pair triaxial with BNC connectors and seal jackets N/A 25 ft/7.6 m pair triaxial with BNC connectors and seal jackets N/A 50 ft/15 m pair triaxial with BNC connectors and seal jackets N/A 25 ft/7.6 m pair triaxial with BNC connectors and seal jackets
Serial Communications N/A None N/A Modbus® RTU via RS-485 or HART (field selectable) N/A None N/A Modbus® RTU via RS-485 or HART (field selectable) N/A None
Control Relays N/A 2 relays, rated 5 amp SPDT, programmable N/A 2 relays, rated 5 amp SPDT, programmable N/A 2 relays, rated 5 amp SPDT, programmable N/A 4 Extra Relays (6 total), rated 5 amp SPDT, programmable N/A 2 relays, rated 5 amp SPDT, programmable
Measuring Accuracy N/A ±1.0% of reading from 1.5 to 40 ft/sec (0.5 to 12.0 m/sec) and ±0.015 ft/sec (±0.0046 m/sec) for velocity below 1.5 ft/sec (0.46 m/sec).
Repeatability & Linearity N/A ±0.25%
Flow Measuring Range N/A 0.07 to 40 ft/s0.02 to 12 m/s
Pipe Diameter N/A SE16A: 0.5" to 4" (15 mm to 100 mm) SE16B: 2" to 48" (50 mm to 1200 mm)
Pipe Materials N/A Any metal or plastic sonic conducting materials, including carbon steel, stainless steel, ductile iron, concrete lined ductile iron, cast iron, PVC, HDPE, PVDF, fiberglass, copper, brass, aluminum, and pipes with bonded liners, including epoxy, rubber, and PTFE.
Operating Frequency N/A SE16A: 2.56 MHz SE16B: 1.28 MHz
Transducer - Operating Temperature Range N/A -40 to 300 ºF-40 to 150 ºC
Electronics - Operating Temperature Range N/A -5 to 140 ºF-20 to 60 ºC
Analog Output N/A Isolated 4-20mA/0-5V, 1000 ohm load max., programmable offset
Hazardous Area Certifications N/A Non-Incendive for Class I Division 2, Groups A,B,C,D Optional: Intrinsically safe for Class I Division 1, Groups A,B,C,D
Approximate Shipping Weight N/A 12 lb5.5 kg
A N/A 10.94 in278 mm
B N/A 7.4 in188 mm
C N/A 5.12 in130 mm
D N/A 10 in254 mm
E N/A 6.46 in164 mm